Which Wire for AC? Wire Size and MCB for 1, 1.5 and 2 Ton ACs
By WireBolt Team · Updated · 6 min read
Quick answer
For most 1 and 1.5 ton split ACs, run a separate circuit in 2.5 sq mm copper wire (phase, neutral and earth) protected by a 16 A MCB. For a 2 ton AC, or any run longer than about 30 metres, use 4 sq mm wire with a 20 A MCB. Always check the maximum current printed on your AC's rating plate before you buy.
An air conditioner is the biggest load in most Bengaluru homes. It can run for hours on a hot afternoon, and its compressor pulls a surge of current every time it starts. Wire that is too thin heats up slowly inside the wall, softens its insulation and loosens connections. That is how many electrical fires start. The fix is simple and cheap if you do it while wiring: give every AC its own circuit, in the right wire size, with the right MCB.
The short answer: AC wire size chart
Use copper wire (never aluminium inside a home), ISI marked, FR or FRLS grade. One circuit per AC, straight from the distribution board.
| AC size | Typical current | Wire size (copper) | MCB | Connect through |
|---|---|---|---|---|
| 0.75 to 1 ton | 4 to 7 A | 2.5 sq mm | 16 A, C-curve | 16 A socket |
| 1.5 ton | 7 to 10 A | 2.5 sq mm | 16 A, C-curve | 16 A socket |
| 2 ton | 10 to 15 A | 4 sq mm | 20 A, C-curve | 20 A AC isolator (or as the AC maker says) |
| Any size, run over about 30 m | – | one size up (4 sq mm) | 20 A | as above |
Why 2.5 sq mm and not 1.5 sq mm?
Every wire size has a safe current limit. Above it the copper heats up faster than the wall around it can take the heat away. For PVC-insulated copper house wire in a conduit, the limits are roughly:
| Wire size | Safe current in conduit (approx.) | Typical use |
|---|---|---|
| 1 sq mm | 10 to 12 A | lights |
| 1.5 sq mm | 13 to 15 A | lights, fans, 6 A sockets |
| 2.5 sq mm | 18 to 20 A | 16 A sockets, 1 to 1.5 ton ACs |
| 4 sq mm | 24 to 27 A | 2 ton ACs, geysers, kitchen power |
| 6 sq mm | 31 to 35 A | main lines, large loads |
Exact figures vary by brand and how many wires share a pipe, so check the table printed on the coil or in the maker's catalogue.
On paper, 1.5 sq mm could carry a small AC's running current. But an AC runs at that current for hours, often in a hot, crowded conduit. Electricians also want headroom for the starting surge and for the day someone replaces the AC with a bigger one. 2.5 sq mm costs only a little more and removes the risk. For lights and fans, 1.5 sq mm is fine. See which wire size for which point.
Which MCB for an AC?
The MCB (miniature circuit breaker) protects the wire, so its rating must never be higher than what the wire can carry:
- 2.5 sq mm wire → 16 A MCB. Correct for almost every 1 and 1.5 ton AC.
- 4 sq mm wire → 20 A MCB. For 2 ton ACs and long runs.
- Never put a 25 A or 32 A MCB on 2.5 sq mm wire "so it doesn't trip". If it trips, find out why. A bigger MCB just lets the wire overheat.
Choose a C-curve MCB. It is made for loads like motors and compressors that pull a short surge when they start, so it won't trip every time the AC kicks in, but it still trips on a real overload or short circuit. If your distribution board has no spare ways, now is the time to move to a bigger one.
How to wire an AC point properly
- Run a dedicated circuit from the distribution board: phase, neutral and earth, all the same size (2.5 or 4 sq mm).
- Use colour-coded wire: red (or brown) for phase, black (or blue) for neutral, green (or green-yellow) for earth. It makes later repairs safer.
- Put the wires in conduit: HMS PVC pipe if they're concealed in the wall or slab, 25 mm if more than one circuit shares the pipe. See our conduit pipe size guide.
- Fit a 16 A socket or a proper AC isolator close to the indoor unit, usually high on the same wall, so the AC's own cable reaches it without a joint. Never plug an AC into a 6 A socket or an extension board.
- Connect the earth. The AC body must be earthed to a working earth pit. Without it, a fault can make the metal casing live. See our house earthing guide.
- Tighten every terminal. Most AC wiring failures start at a loose screw that heats up over months.
How much wire do you need?
Measure the route the wire will take, not the straight-line distance: along the wall, up to the ceiling, across, and down to the AC point. Then:
Wire length = route length × 3 (phase, neutral, earth) + 10% extra
| Route from the board | Wire needed | Buy |
|---|---|---|
| 10 m | about 33 m | one 90 m coil covers 2 such AC points |
| 15 m | about 50 m | one 90 m coil per AC, with some left over |
| 25 m | about 83 m | one 90 m coil, or 180 m for two ACs |
Buying a full coil in each colour is usually cheaper than buying exact lengths, and the leftovers go into the next point. Wires come in 90 m and 180 m coils.
Common mistakes that burn AC wiring
- Running the AC from a light circuit or an existing socket that also feeds other appliances.
- Using an extension board or a 6 A socket with an adapter. The plug and socket heat up and melt.
- Aluminium or "local" wire without an ISI mark. It looks cheaper but has less copper inside.
- Oversized MCB (25 or 32 A) on thin wire. The wire burns before the breaker trips.
- No earth connection. A fault in the AC can then make its metal body live.
- Joints hidden inside the wall with only tape. Join wires inside a junction box with proper connectors.
Before you call the electrician
Write down your AC's tonnage and the maximum current from its rating plate, and measure the route to the distribution board. With those three numbers, your electrician can confirm the wire size and MCB in a minute. You can also order the wire, conduit and fittings in advance, so the job doesn't stop halfway for a shop run. Browse all house wires.
This guide is general information for homes in Bengaluru. Electrical work should be done by a licensed electrician who can check your actual load, wiring and supply. Last checked 19 November 2026.